See all 11 partsA code on the display?
20 fault codes for the FJ 7 PRO ROOFTOP, from Dometic's own documents. Tap one to see what to check.
ADB 8 fast + 8 slow beeps13-pin connector not seated
Likely cause: The 13-pin plug is loose at the main PCB or the transfer PCB.
Dometic's checks, in order: Check and reseat the plug at both ends and inspect for damaged pins.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
E0Communication failure
Likely cause: Lost communication between display and main boards, or loss of outdoor power supply.
Dometic's checks, in order: Check the communication cable at both PCBs and repair if loose/damaged; test with a spare display PCB; if still faulty replace the main PCB.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
E1Room temperature sensor fault
Likely cause: Indoor ambient sensor open or short circuit.
Dometic's checks, in order: Check the room-sensor reading via the ADB; replace the sensor if abnormal.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
E2Evaporator coil sensor fault
Likely cause: Indoor coil sensor open or short circuit.
Dometic's checks, in order: Check the coil-sensor reading via the ADB; replace the sensor if abnormal.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
E3Condenser coil sensor fault
Likely cause: Outdoor coil sensor open or short circuit.
Dometic's checks, in order: Check the coil-sensor reading via the ADB; replace the sensor if abnormal.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
EACurrent sensor fault
Likely cause: The system detected no current.
Dometic's checks, in order: If shown immediately at switch-on it is a hardware fault: replace the main PCB. If shown after the compressor starts (very low compressor current for over 30 s at 35 Hz or more), check refrigerant charge and repair leaks.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
Show all 20 codes
ECNot documented
Likely cause: Sheet gives no cause.
Dometic's checks, in order: Contact Dometic.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
EEOutdoor EEPROM fault
Likely cause: Main board cannot read its EEPROM data.
Dometic's checks, in order: Replace the main PCB.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
EHNot documented
Likely cause: Sheet gives no cause.
Dometic's checks, in order: Contact Dometic.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
ELLIN-BUS / CI-BUS communication failure
Likely cause: Bus communication failed during the start-up self-check.
Dometic's checks, in order: Check the LIN/CI-BUS cable and connections and the RV's master control panel; if the fault persists replace the display PCB.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
EPNot documented
Likely cause: Sheet gives no cause.
Dometic's checks, in order: Contact Dometic.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
EUNot documented
Likely cause: Sheet gives no cause.
Dometic's checks, in order: Contact Dometic.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P1Supply voltage too low (under-voltage protection)
Likely cause: Mains input has dropped below about 130 V (+/-5 V).
Dometic's checks, in order: Check the 240 V supply reaching the unit (lead, site power or generator).
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P2AC over-current protection
Likely cause: Running current is above the unit's limit.
Dometic's checks, in order: Check supply voltage, confirm both fan motors run, measure compressor current; replace the compressor if its draw is abnormal, otherwise the main PCB.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P3Supply voltage problem (not in the main table)
Likely cause: Unstable or unsuitable supply, commonly a generator that is undersized or not pure sine wave.
Dometic's checks, in order: Check the generator size and quality (pure sine wave, inverter-compatible).
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P4Compressor discharge pipe too hot
Likely cause: Discharge-tube temperature is over the protection limit.
Dometic's checks, in order: Read the discharge temperature through the ADB; replace the sensor if the reading is wrong, otherwise check coil temperatures and refrigerant charge (leak-test and recharge if low).
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P5Evaporator coil too cold (cooling mode)
Likely cause: Indoor coil temperature has fallen too low while cooling. On early Freshjet ADBs (built before week 40/2023, ADB serial below 340xxxxx) a faulty display PCB can also throw a spurious P5 and change settings by itself (Dometic bulletin 130324).
Dometic's checks, in order: Check the indoor fan runs and read the coil sensor through the ADB; replace the sensor if wrong, otherwise check refrigerant charge. If the early-ADB symptoms match, the fix is replacement display PCB 4450031469 (bulletin 130324).
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P6Condenser coil too hot (cooling mode)
Likely cause: Outdoor coil temperature is too high while cooling.
Dometic's checks, in order: Clear any blockage at the condenser air inlet/outlet, check the condenser fan, read the coil sensor through the ADB; replace the sensor if wrong, otherwise check refrigerant charge.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P7Evaporator coil too hot (heating mode)
Likely cause: Indoor coil temperature is too high while heating.
Dometic's checks, in order: Check the indoor fan and the coil sensor reading through the ADB; replace the sensor if wrong, otherwise check refrigerant charge.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
P8Outdoor temperature out of range
Likely cause: Outside air below 0 C in cooling mode, or above 32 C in heating mode.
Dometic's checks, in order: Confirm the right mode was selected; check the outdoor sensor is mounted where it belongs (not touching the compressor or hot pipework) and reads correctly via the ADB; if all OK replace the main PCB.
Source: Freshjet 4 & 7 series Error codes, page 1. Open the document
Documents for the FJ 7 PRO ROOFTOP2 documents from Dometic
- FJ 7 PRO ROOFTOP spare parts listParts list · released 10 Nov 2021
- Freshjet 4 & 7 series Error codesTroubleshooting guide · released Jun 2024 · Open it
Where these numbers come from
We don't invent part numbers. Every number on this page is copied from Dometic's documents listed above, with the page. If a document is in doubt we hold the part back and say so.
Not sure it's an FJ 7 PRO ROOFTOP?
On a roof-top air conditioner it's on the ceiling unit inside: take off the return-air grille or lift out the filter and look up. Otherwise it's on the roof unit under the shroud.
How to read the plate All Dometic modelsAll 11 parts for the FJ 7 PRO ROOFTOP
Every part Dometic's documents list for the FJ 7 PRO ROOFTOP, grouped by area. Tap a part for its price, where to buy it and the page it came from.
Prices last seen between 16 Sep 2026 and 27 Oct 2026. Each price shows its own date. The shop's own page is final.
Burner & flame1 part
-
Callout 2 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops
Seals & doors1 part
-
Callout 9 · FJ 7 PRO ROOFTOP spare parts list
$36.95 last in stock · last seen 16 Sep
Compare 2 shops
Electrical4 parts
-
Callout 3 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops -
Callout 5 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops -
Callout 8 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops -
Callout 11 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops
Other parts5 parts
-
Callout 1 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops -
Callout 4 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops -
Callout 6 · FJ 7 PRO ROOFTOP spare parts list
$240.00 last in stock · last seen 16 Sep
Compare 2 shops -
Callout 7 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops -
Callout 10 · FJ 7 PRO ROOFTOP spare parts list
None in stock 2 shops list it · last seen 27 Oct
Compare 2 shops
What the fit words mean
- Very likely fits 11 parts. From the maker's documents for this model, with a condition or a caveat we explain on the part.
Why 11 parts here aren't marked "Fits": Listed against this model in the Airconditioner FJ 7 Pro parts list.
Parts shared across a range are often named after the first model they were made for, so a name may mention a different model. That doesn't mean it won't fit yours.
Is this my air conditioner?
Check the plate on your air conditioner says FJ 7 PRO ROOFTOP.
- MOD. NO.
- FJ 7 PRO ROOFTOP
- Item or product code
- 9620001685
On a roof-top air conditioner it's on the ceiling unit inside: take off the return-air grille or lift out the filter and look up. Otherwise it's on the roof unit under the shroud.
Where's the plate on a Dometic air conditioner?
Not your model? See all Dometic models or ask us to find it.