Autoterm FLOW liquid (coolant) heaters FLOW-5D / 5B / 14D - fault codes

All 25 codes, what each one means and what to check, from AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024.

01Overheating: coolant temperature above 120 C at a sensor.

Likely cause: Air lock in coolant circuit, pump fault, sensor fault or unsuitable antifreeze.

Autoterm's checks, in order: Bleed the circuit, check pump and sensors, check antifreeze rating.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

03Temperature sensor 1 fault.

Likely cause: Short or open circuit in sensor wiring.

Autoterm's checks, in order: Replace the sensor assembly.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

04Temperature sensor 2 fault.

Likely cause: Short or open circuit in sensor wiring.

Autoterm's checks, in order: Replace the sensor assembly.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

05GASFlame detector fault.

Likely cause: Short to frame or open circuit in detector wiring.

Gas fault: get a licensed gas fitter

Turn the gas off at the bottle and run the appliance on another power source until it's checked. Only a licensed gas fitter should work on the gas side.

Autoterm's checks, in order: Check the flame detector.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

06Control unit temperature sensor fault.

Likely cause: Internal sensor failure (not replaceable separately).

Autoterm's checks, in order: Replace the control unit.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

09Glow plug fault.

Likely cause: Short or open circuit, or control unit fault.

Autoterm's checks, in order: Check the glow plug and control unit.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

10Air blower speed below rated.

Likely cause: Debris obstructing impeller or impeller hitting cover.

Autoterm's checks, in order: Check wiring and clean the air blower.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

12Shut down: voltage above 16 V.

Likely cause: Faulty regulator, charger or wiring.

Autoterm's checks, in order: Check voltage at heater connector, fuses, battery and regulator.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

13All start attempts failed (two attempts).

Likely cause: Fuel supply, blower or exhaust problem, or blocked glow-plug opening.

Autoterm's checks, in order: Check fuel line, pump, blower and exhaust; clean the combustion chamber plug opening.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

14Coolant pump fault.

Likely cause: Short or open circuit in pump wiring.

Autoterm's checks, in order: Check pump wiring and pump; clean pumping elements.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

15Shut down: voltage below 10 V.

Likely cause: Weak battery, fuses or wiring.

Autoterm's checks, in order: Check voltage at heater connector, fuses, battery and wiring.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

16Ventilation time exceeded.

Likely cause: Flame detector not cooled by purge.

Autoterm's checks, in order: Check air intake and exhaust; check and replace flame detector if needed.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

17Fuel pump short circuit.

Likely cause: Short in fuel pump wiring.

Autoterm's checks, in order: Check the fuel pump and wiring.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

20No communication between heater and control panel.

Likely cause: Short or open circuit in the panel wiring.

Autoterm's checks, in order: Check the 5 A fuse, circuits and terminals.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 26. Open the PDF

21GASFlame blew out during warm-up.

Likely cause: Lack of fuel or air, fouled heat exchanger or blocked exhaust.

Gas fault: get a licensed gas fitter

Turn the gas off at the bottle and run the appliance on another power source until it's checked. Only a licensed gas fitter should work on the gas side.

Autoterm's checks, in order: Check intake, exhaust and fuel supply; replace pump or flame detector if needed.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

22Fuel pump open circuit.

Likely cause: Break in fuel pump wiring.

Autoterm's checks, in order: Check the fuel pump and wiring.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

24Rapid temperature change at one sensor.

Likely cause: Poor coolant circulation causing local overheating.

Autoterm's checks, in order: Bleed the circuit, check pump and sensors, check antifreeze.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

25Coolant heating up too quickly.

Likely cause: Heater entered cool-down three times within 6 minutes in one cycle.

Autoterm's checks, in order: Bleed the circuit, check pump and sensors, check antifreeze.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

27Air blower fault: motor not rotating.

Likely cause: Motor movement obstructed.

Autoterm's checks, in order: Check the blower and fuel system as directed.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

28Air blower fault: uncontrolled rotation.

Likely cause: Possible fault in the 5 V supply to the control unit.

Autoterm's checks, in order: Check blower and control unit supply.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

29GASIgnition failed repeatedly while running (over four tries).

Likely cause: Fuel supply problem: clamps, line seal, pump nozzle or pump capacity.

Gas fault: get a licensed gas fitter

Turn the gas off at the bottle and run the appliance on another power source until it's checked. Only a licensed gas fitter should work on the gas side.

Autoterm's checks, in order: Check fuel line clamps, seals, pump nozzle and pump delivery.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

30GASFlame blew out because voltage dropped.

Likely cause: Blower stopped when vehicle voltage dipped, e.g. long cranking.

Gas fault: get a licensed gas fitter

Turn the gas off at the bottle and run the appliance on another power source until it's checked. Only a licensed gas fitter should work on the gas side.

Autoterm's checks, in order: Check the battery and wiring.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

37Heater locked after three failed starts (code 13 three times).

Likely cause: Repeated start failures; lock stops excess fuel entering the chamber.

Autoterm's checks, in order: Find and fix the cause, then unlock the heater.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

50No communication between control panel and router (modem).

Likely cause: Short or open circuit in wiring.

Autoterm's checks, in order: Check the 5 A fuse, circuits and terminals.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF

78GASFlame blew out during operation (information only).

Likely cause: Minor fuel delivery issue.

Gas fault: get a licensed gas fitter

Turn the gas off at the bottle and run the appliance on another power source until it's checked. Only a licensed gas fitter should work on the gas side.

Autoterm's checks, in order: Check fuel line clamps, seals and pump nozzle.

Source: AUTOTERM liquid heaters FLOW-5D / FLOW-5B / FLOW-14D user's manual with installation instructions, EN v01.2024, page 27. Open the PDF